This Control System can be readily installed in existing housing units or remodeled apartments, without need for any additional electrical-line work.
The installation process is simple.
The existing boiler temperature controllers are changed to wireless temperatures, and a battery-powered wireless temperature controller is installed in each room.
Finally, the manual valve of the hot-water distributor is changed to an electric valve.
![]() |
KRC-500RF Color Living-Room Wireless
Temperature Controller
Control Mode
Temperature : 5℃ ~ 40℃, 1℃Unit Intermittent heating : 3-4-5-6-9-12-15-20-25-30-60 min/hour (Automatically set temp. at 30℃) Timed heating : 24-hour timed heating possible for all rooms, time set by the hour Specifications Certified radio communication device (KDT-KRC-500RF) Wireless communication : 447MHz, bidirectional 2400bps, 3-phase ID configuration, crossed-lines prevention Color graphic : 2.8inch TFT 65K Color touch screen, 32bit CPU embedded Freeze protection : Automatically started when the current temp. drops below 5℃ Dimensions : 72 × 145 × 13mm Characteristics Can be easily applied to various heating structures (regional/individual) without the need to add electric lines Easy checking and control of the heating status of all rooms with the color screen |
![]() |
KRC-220RF Color Living-Room wireless Temperature Controller
Control Mode
Temperature : 5℃ ~ 40℃(indoor temp.), 1℃Unit, ice prevention starts at 5℃ Intermittent heating :3-4-5-6-9-12-15-20-25-30-60 min/hour (Automatically set temp. at 30℃) OUT mode : Heating OFF when set to the Going OUT mode (autoset temp. at 5℃) Specifications Certified radio communication device (KDT-KRC-220RF) Wireless communication : 447MHz, bi-directional 2400bps, 3 phase ID configuration, crossed lines prevention Batteries : use approx. 1 year, Alkaline LR6(AA) × 2 Dimensions : 120 × 100 × 23mm Characteristics The power consumption during the waiting period is minimal (below approx 18uA) Hence, the battery use time is long. |
![]() |
MC-3100RF Wireless Valve Control Box
Specificaions
Boiler connections : Direct communication link with the boiler using the wireless living-room temperature controller, or uses a repeater [RB-300/RB-400P] to connect with the boiler room controller Wireless communication : Communicates with the color living-room wireless temperature controller. 447MHz bidirectional 2400bps. 3-phase ID configuration, crossed-lines prevention Certified radio communication device [KDT-MC-3000RF] * The specifications and characteristics are identical to those of MC-3000 |
![]() |
MC-500RF Mini Wireless Valve Control Box
Specificaions
Power : AC220±10% 50/60Hz, Power cord 1M Temperature controllers : Connections for up to two wireless Temperature controller (KRC-220RF) Valve drivers : Choose between AC220V/AC21V - up to 2 Valve hardening prevention function : open 1 time / 72 hours Wireless communication : 447MHz bi-directional 2400bps, 3-phase ID configuration. prevention of crossed lines Certified radio communication device (KOT-MC-500RF) Dimensions : 85 × 85 × 42mm Characteristics Perfect for installation in residential housings and officetels with under four zone Can apply to vatious heating structures with different system conbinations Creates lowcost systems. |
![]() |
RB-300/400P
Specificaions
Power : AC220V±10% 50/60Hz Power cord : 1M Connections for KRC-500RF Boiler connection (RB-300) : Communication linkage or relay contact points (NO-COM-NC) Pump Control(RB-400P) : Pump under 600W Dimensions : 62 × 85 × 42mm |
![]() |
KVA-300 Motorized Zone Valve(Ball Type)
Power consumption : AC21V, 2.5W(While operating)
Motor/cord : AC magnet motor, VCTF 0.5㎟ × 31M Rotational torque : 20kgf/cm Permissible valve differential pressure : 4bar Closing pressure : 10kg/㎠ Operating time : 15seconds - 15seconds (Open - Closed) Valve Size : 15A, 15S (valve socket) Special Feature Electrically safe as it is operated at a low voltage (AC21V) Easy manual control and identification of open/close state No direction restraints, allowing free installation |
![]() |
KVA-400 Motorized Zone Valve(Disc Type)
Power consumption : AC21V, 2.5W(While operating)
Motor/cord : AC magnet motor, VCTF 0.5㎟ × 31M Rotational torque : 20kgf/cm Permissible valve differential pressure : 4bar Closing pressure : 10kg/㎠ Operating time : 11seconds - 11seconds (Open - Closed) Valve Size : 15A, 20A, 25A Special Feature Electrically safe as it is operated at a low voltage (AC21V) Easy manual control and identification of open/close state Comes with directions (install in the return pipe) |